Zhejiang Province Zhuji City Fudelong Business Co., Ltd.

JFT Series square counter flow type FRP cooling tower

JFT Series square counter flow type FRP cooling tower
Product Detailed

square counter flow type FRP cooling tower
Easy accessible driving system.
CTI STD-201 Certification.
Patented ( SX-COMB )

 This model choosing table is applicable in area with atmospheric pressure at the range from 79.99Kpa to 101.33Kpa.

Design conditions of JFT Series , water inlet temperature: t1=37°C, water outlet temperature: t2=32°C, wet bulb temperature t=28°C.

Take the following working conditions as an example to choose cooling tower. For example: water inlet temperature: 37°C, water outlet temperature: 32°C, wet bulb temperature :28°C, Δt : 5°C, circulating water amount needed :200m3/h.

1),From the point of water-inlet temperature 37°C make line up straightly meeting the wet bulb temperature of 28°C curve at point (1);

2),From point (1) make horizontal line meeting the Δt 5°C curve at point (2)

3),  From point (2) make line up straightly meeting the circulating water amount of 200m3/h curve at point (3);

4),From point (3), The choosing model that corresponds with cooling tower feature curve is JLT-200.

    Model : JFT-200(L,UL)(Z,G)
    Square Counter Flow Model Cooling Tower
    200 means circuit water amount
    (L, UL) Standard model / L : Low noise model / U : Ultra low noise model
    (Z, G ) Z : medium water Temp. model G : High water Temp. model. 
Rectangular counterflow cooling tower JFT series

 

1,Tower Case :made of FRP compound materials (Fiber Glass reinforced ). The body’s exterior adopts imported materials which contain stabilization material resisting ultraviolet radiation. So, it has smooth and clean surface, and it is able to bear aging, 
2,Fan:choosing the special Fan with variable section, twist and pitching blade. The fan works at an equal speed, a low self moving pressure, a saving-energy use and a low noise. Moreover, Fan can be changed the fixing angle of the blade to meet the work d
3,Motor: choosing the special electric motor with whole sealed cooling tower, 380V/3φ/50HZ. It has excellent capability of waterproof IP44, so can be safely used in warm and humid environment.
4,Fill : with Rectangular conterflow Model fill, made of PVC film which formed with vacuum forming process, have strong capability to resisting ultraviolet radiation and corrosion. It has highest thermal exchange capability, long life span and low resista
5,Water distribution system : as it is adopted the fog shaping distribution system, guarantee equal drain, low water supply pressure and also nozzles are not closed easily than rotating water distribution system of rotundity cooling tower
6,Eliminator : its is the Model of preventing the drift loss by inertia, it reduce the drift loss to lowest level. 
7,Steel Structure : all be treated with rust-removing, hot dipped galvanized steel. All can bear corrosion, have high strength, be easily assembled and have elegant surface.
8,Bearing –all rotating parts are used bearing imported from Japan, with high precision and low servicing rate.
1. Motor : whole sealed, 380V/3φ/50HZ
2. Motor frame : hot dipped galvanized steel
3. Fan stack : FRP
4. Fans : aluminum alloy
5. Eliminator : PVC
6. Water distribution axis : PVC
7. Fill : PVC
8. Case : FRP
9. Louver : FRP
10. Water-dropping noise isolator :(low and           ultra low noise): nylon and hot dipped           galvanized steel
11. Leg : hot dipped galvanized steel
12. Cold water basin : FRP
13. Nozzle : ABS
14. Inlet water flange : HT200
15. V- belt reducer
16. V-belt 

 

Spare Parts Provided for Jinling Cooling Towers

1,FDL Reduces with Visible Equipment forAdding Oil

2,Vibration Isolators (Rubber and Spring)

water inlet temp.T1=37°C,water outlet temp.T2=32°C,Dry Bulb Temp DBT=31.5°C Wet Bulb Temp WBT=28°C,RangeTs=5°C,barometric P=99400Pa

 



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.